Open-access Numerical simulation of a wet cooling tower

Abstract

A numerical model to predict the flow field in and around a counter flow induced draft wet cooling tower was developed and tested. The numerical model consisted of the Thiart fan model, a Lagrangian droplet model and a packing model. The droplet model exposed the need to model the effect of the packing on the droplets and a simplified model was implemented to prolong the droplet retention time in the packing. The full cooling tower model predicted trends, at design conditions and with a wind present, which compared well with results reported in the literature.


location_on
South African Institution of Mechanical Engineering Research and Development Journal, University of Stellenbosch, Private Bag X1, Matieland, Cape Town, Western Cape Province, ZA, 7602, Tel: +27 21 808 4091 - E-mail: gillianc@sun.ac.za
rss_feed Stay informed of issues for this journal through your RSS reader
Go to top