Open-access Reduction of Langelier index of cooling water by electrolytic treatment with stainless steel electrode

Abstract

The efficiency of electrolytic treatment in reducing the Langelier saturation index (LSI) of the cooling water from a cooling tower of a textile industry was investigated. Sacrificial anodes were employed which prevent obnoxious chlorine generation. A series of batch experiments using stainless steel electrodes were conducted with 4 different current densities (5, 7, 10 and 15 A/m2) and 6 different electrolysis times (20, 30, 40, 50, 60 and 70 min). The use of 7 A/m2 for 50 min electrolysis time yielded a satisfactory efficiency in reducing the LSI index from 2.57 to zero, indicating that the treated water was of sufficient quality to be reused in the cooling process.

cooling water; electrolytic treatment; hardness; Langelier saturation index; water reuse