Abstract
Axial flow fans installed at large-scale air-cooled condensers (ACCs) may operate under distorted inlet air flow conditions. These inflow conditions as well as the fan's surroundings cause a variation in blade loading as a function of the blade's rotational position. An investigation was launched to simultaneously measure the inlet air flow and the resultant blade and gearbox loading conditions of a single fan located on the edge of a large-scale ACC. Measurements were recorded over a period of five days where it was found that the air flow through the fan is highly dependent on the wind speed and direction. Subsequently, the pressure rise over the fan, which affects the blade loading, is highly dependent on the atmospheric wind speed and direction as well. In addition, the fan blade was found to vibrate at its own natural frequency of approximately 6 Hz when excited by the aerodynamic loading.
axial flow fan; air-cooled condenser