Abstract
Industries in South Africa are prioritising energy efficiency in the installation of new machinery and are investigating reductions in power consumption in current production lines. This interest in energy consumption has greatly increased as a direct result of the country's significant electricity price increase request of 16% per year from 2012 to 2018 [1]. The cost, as well as recent environmental assessments, has made industries aware of their carbon footprints and the need for improved efficiency. This paper reports on the design of a multipurpose energy efficient apparatus to test the power efficiency of common industrial equipment and the effects of incorrect installations. It has been achieved with the construction of a 30 kW testing apparatus, capable of running a variety of motors, couplings, and belts. Motor testing was conducted to indicate the advantage of using high efficiency 4-pole induction motors compared to standard efficiency motors, as well as the advantage of accurately matching power usage to motor capacity. Fluid couplings are often used in the absence of variable speed drives for high torque start-ups. The long term running of these couplings is shown to be inefficient, and thus an investigation into number of start-ups versus run time is required to indicate a more viable option.
1 Introduction
South African industries have recently felt the pressure of continuously increasing electricity prices. These price hikes result in higher production costs, and inevitably increase overall costs to consumers. South Africa was previously known to be among countries with the least expensive electricity in the world [2]. This has resulted in many industries cutting corners in terms of energy efficiency since it was more cost effective to let production lines remain as they were rather than purchase more efficient equipment, and/or installing power transmission devices correctly. This mind-set has since changed, and this paper assesses the design of a test rig capable of investigating the power savings that can be gained from correct equipment purchases and installation practices [3], while considering energy efficiency during the testing process. There is also a need for thorough investigation into the power loss associated with misaligned couplings, incorrectly tensioned belts, low efficiency motors, and the use of fluid couplings as opposed to variable speed drives (VSD).
To accomplish this testing, a rig design capable of accurately measuring the power loss resulting from inadequate installation or misuse in each of the power transmission devices is required. The testing apparatus must be designed to mimic the industrial applications of the equipment to be tested. It must be capable of simulating a hard- and soft-start, and run at specified speeds and torques while allow for any common bad installation practices to be accurately induced. This test rig must be capable of testing the power efficiency of electric motors, couplings and belts, and be capable of accurately applying various forms of misalignment on the components for efficiency measurements to mimic incorrect installation practices.
This paper demonstrates the energy and possible efficiency losses caused by incorrect installation methods and improper equipment selection such as running electric motors at incorrect power ratings, and fluid couplings for extended periods of time. Testing results for the efficiency of belt tensions and for coupling misalignments, has also been conducted, but not presented in this article [4].
A brief summary of fluid coupling and motor losses is discussed in Section 2. Sections 3 and 4 respectively offer the design of the test rig and the testing methodology. Section 5 details the results obtained from varying both fluid coupling and motor parameters. Section 6 summarises the report with concluding remarks.
2.1
Fluid Coupling LossesFluid couplings are often used in industry to prevent damage to equipment when a loaded system is started up without the use of a VSD. The start-up torque of a loaded motor can be up to three times its maximum torque rating which can result in severe equipment damage. The use of a fluid coupling allows for a lag on torque transmission from the drive shaft to the driven equipment, resulting in what is known as a soft-start, similar to that of a VSD, which would ramp the start-up speed of the motor.
A concern with the use of a fluid coupling in lieu of a VSD, is however the continuous running efficiency. A VSD requires a standard coupling of the motor and driven equipment which yields a more efficient form of power transmission than a fluid coupling. A fluid coupling relies on a fluid rotating in a drum for the mating coupling flange to rotate. In this system there are significant losses, rendering the use of a fluid coupling for a few start-ups and lengthy run times, unsuitable. The results of this research can lead to better informed decisions when having to make a choice between a VSD or a fluid coupling.
It is also important to note that fluid couplings should only be used in high inertial systems where the rotational inertial of the coupling itself does not significantly affect the total inertia of the system. These are only to be used in systems where the use of a VSD is impossible and the system is not required to run for extended periods of time.
2.2
Motor LossesElectric motors are used in almost all power drive applications. They account for 60% of industrial energy consumption, and using well-known low cost efficiency techniques can save up to 18% of this consumption [5].
It is commonly known that the use of high efficiency motors and VSDs can improve overall efficiency. The extent of this efficiency gain is a vague value which is addressed in this paper. This investigation will also assess the use of correctly rated motors for each application [6].
3 Test Rig Design
To determine machinery energy efficiency, a test rig was required to measure power efficiency plus speed and torque loading on an electric motor. The rig also had to allow for intentional misalignment of both the radial and angular coupled shaft axis [7] to measure efficiency losses in coupling misalignment. An additional lay-shaft was to be included to increase the versatility of the test rig and to allow for the testing of various belt transmission efficiencies with intentional under-tensioning and misalignment.
Typical dynamometers convert load energy applied to rotating machinery into heat energy which is dissipated into the environment [8]. This energy cannot be recovered. The design specifications from the customer required a fully loaded 30 kW system, the extent and scale of which resulted the need to design an energy efficient test rig. A smart electrical recirculating dynamometer design was therefore considered and a system using frequency inverters in conjunction with an intelligent control system which allowed a drive motor to run an identical motor acting as a generator, was constructed. A load could be set on the generator and the power fed back to the drive motor, requiring only a small percentage of energy from the main power supply to supplement the losses in the system. A decision was made to make use of two standard 380 V, 4 pole, 30 kW electric induction motors for the purposes of the coupling and belt testing. The motors were positioned facing each other to allow for direct coupling with space for the tested equipment to be placed in between, and with an offset lay shaft parallel for belt testing. If another motor was to be tested, the drive motor would be swopped out accordingly. A similar technique was used by the Belt testing Centre in Springfield, Missouri [9]. This design was significantly adapted to allow for other testing aspects to be conducted on the same set-up.
The control system was designed to allow for both gradual speed and torque loading through the use of a VSD, or for a maximum load start-up, or direct-on-line start (DOL). Depending on the testing criteria required, a DOL start would measure start-up efficiencies, while the VSD was used for measuring running efficiencies without applying unnecessary strain on the motors and coupling components. A DOL start is primarily included in this design for use with fluid coupling testing.
The system software was capable of constantly measuring and recording the values of torque, speed, and temperature, while simultaneously calculating the power and efficiency of the required manual input criteria. In the case of a DOL start-up, a high speed capture was included to ensure adequate resolution of the data over a short time frame. This test could retrieve data at a 1 kHz sample rate, but was limited to 750 data points as which point it reverted back to the 1 Hz sample rate. This was due to the programmable logic controllers (PLC) being saturated before the reading could be sent to the software.
Figure 1 is a schematic illustration of how the Exigo EcoDyn system works. The component labelled Exigo EcoDyn is the controller consisting of PLC and software which is responsible for making the system run as required. This controller maintains the power input to the drive motor at the correct levels by taking power from the generator, and by adding power from the main supply to compensate for losses. The controller manages the two frequency inverters, Danfoss VLT Type IP21 30 kW. These frequency inverters provide power to the drive motor as well as receive power from the generator.
The frequency inverters are responsible for transferring power from the generator to the motor. This occurs by using inverters to convert the generated power from AC to DC. The DC is then transmitted to the drive inverter which converts it back to AC to supply the drive motor. Using this method simplifies problems which would have occurred with phase mismatch, and also matches the frequencies of the generated power with the power supply from the mains. The EcoDyn uses inputs from the Watt meters, sine wave signal filters, torque, and speed transducers to control and maintain the correct power at all times.
A Watt meter is positioned directly before the drive motor to allow for the most accurate control of the drive by measuring and controlling the power received by the drive motor. The sine wave filter is positioned before the Watt meter to convert the square waves to natural sine waves ensuring an accurate reading from the Watt meter.
The drive and load (driven) motors are orientated facing each other so that direct coupling can be achieved through the use of the various test couplings. For the belt testing, a lay-shaft was included to allow for the offset power transmission. This lay-shaft is supported by two self-aligning bearings, which are mounted on two sliding rails for belt tensioning adjustment. A mounting base frame of the test rig can be seen in figure 2.
Base plates were designed for the motors to mount to the frame, and to allow for belt alignment and tensioning as well as coupling radial and angular misalignment. The top base plate on the drive side only allowed for the belt alignment and tensioning, while the top base plate on the load side allowed for both belt and coupling adjustments. The bottom base plates (referred to as the base plates) allowed for axial alignment to account for the various spacing requirements of different couplings.
Adjustments were achieved through the use of slots cut into the base plates, using bolts as pins to hold the required position. On the drive side, the slots were square to the frame, allowing controlled straight movement. The load side however, has both straight and rotationally cut slots to allow for either belt or coupling alignment. The angle of rotation for coupling misalignment was constrained rotationally at the centre point of the coupling. The base frame with the base plates in position can be seen in figure 3.
Figure 3 shows that each motor base plate is a combination of two separate plates which are allowed to slide freely over each other within the constraints of the slotted holes. The base plates only allow longitudinal movement relative to the base frame while the top base plates allow for radial and rotational movement relative to the base plate. The motor positions were accurately measured and set into the required positions using a Lenovo inclinometer alignment tool. The Lenovo tool resulted in misalignment accuracies of up to 0.01° angular misalignment and 0.01 mm radial misalignment. Belt tensions were set and verified with a sonic belt tensioning device, while alignment was ensured through the use of a belt alignment laser.
The final aspect of the test rig is its ability to accurately measure power transmission through the devices. Simply taking electrical power measurements from the motor controllers was not sufficient as this included motor inefficiencies, resulting in accumulative losses for each component tested. Physical torque and speed measurements were required for accuracy. The speed was measured through the use of speed transducers mounted to the back end of the motor shaft and the torque measurements were achieved by measuring the resultant force on the motor feet.
The motor was supported by its central shaft. This was achieved by supporting the motor output shaft on a motor stand mounted at the front, and a dummy rear shaft through a cradle system at the back. The cradle is mounted directly to the motor feet, extending up to create a dummy rear shaft. The dummy rear shaft is pressed fit into the movable back stand, ensuring no relative motion between the dummy shaft and the movable back stand. This rear shaft is then supported by the rear motor stand as illustrated in figure 4 below. These motor stands were mounted directly to the motor top base plates discussed above. To prevent interference between the pedestals, the base plate, and the top base plate, the pedestals were mounted from underneath the top base plates with the use of countersunk cap screws.
Mounting the motor in this manner, allows it to rotate freely about its central shaft. This offers an opportunity to control how the rotation is restricted, thus offering an opportunity to accurately measure the physical motor torque through the reaction of the motor load. This motor force is translated to a calibrated load cell through a set lever arm mounted to the rear dummy shaft. The motor mounting and torque lever-arm can be seen in figure 5 below. The torques of both the drive and load motor are measured using the same technique.
4 Testing Methodology
The designed testing apparatus is capable of testing a variety of belts, couplings, and motors. This paper contains only the test results for the efficiency of fluid couplings on a high inertial system, and the efficiency of electric motors at percentage variations of their maximum loads. Results and testing sequences for coupling misalignment efficiency and belt tension efficiency can be located in reference 7.
4.1
Fluid couplingA fluid coupling is designed to reduce the rate at which torque is initially transmitted, thus preventing shock loading. During a hard-start, a motor may put out up to three times its maximum torque output.
An investigation into the running efficiency of a fluid coupling was also required because the running losses of a fluid coupling may make it inefficient when run for extended periods of time with few start-ups. These tests show under what conditions a fluid coupling can be beneficial to a system, based on energy usage and depending on the number of start-ups and intended duration of the run time. It may be assumed that due to the nature of this coupling, the running efficiency will be lower than that of a solid coupling, and is therefore not an appropriate choice if the machinery is expected to operate continuously for long periods of time.
The fluid coupling tests were conducted using a DOL procedure. The tests included the high speed capture mentioned above to accurately plot the initial start-up torque and displacement. A fluid coupling was inserted on the drive motor side in lieu of a solid coupling connecting the drive motor to the main shaft. The efficiency of the solid coupling connecting the main shaft to the load motor is known for the tests. Due to the size of the coupling required, sufficient space had to be made available between the motor base, and the main shaft bearing support. The start-up torque and rotational displacement for both a solid coupling and a fluid coupling were compared.
4.2
MotorTesting of the motors was conducted to ascertain the effect on efficiency when using a motor significantly below its maximum power output, and to ascertain the efficiency gain when using a high efficiency motor.
Data was obtained by running the motors at synchronous speed at set loads. Efficiency measurements were only taken after a stable temperature was reached. Testing was conducted at 10% intervals of full power from 50% to 100%. Motor efficiency was measured as a comparison of the electrical power in and the mechanical power out, measured by the cradle system.
5 Results and Discussion
5.1 Fluid coupling
Figures 6 and 7 indicate the rotational displacement of the drive and load motors for both the directly coupled system and the fluid coupling coupled system respectively. An element type coupling of a known efficiency was used to directly couple the motors. The system was started purely under inertial load, with no other loads applied. The results indicate that the fluid coupling increases the time it takes to accelerate the motor to full speed, in other words, it reduces the shock loading. This is evident in figures 6 and 7 which indicate the rotational displacement of the drive and driven motor for both scenarios.
The difference in rotational displacement for the directly coupled scenario is negligible; there is no rotational difference as can be seen in figure 6. The scenario which includes the fluid coupling however (figure 7), shows a distinct lag in rotational displacement between the drive and the load motor. This result is expected as there is a lagged acceleration between the drive and the load motor due to the intended nature of the fluid coupling. The rotational displacement lag between the drive and load motors result in a time delay for the load motor to reach maximum speed. This acts to reduce the maximum torque met by the load motor during a hard or DOL, start.
Figure 8 shows a graph of the hard-start start-up torques of the drive motor with a fluid coupling, as well as without a fluid coupling. The hard-start without the fluid coupling accelerates to full speed in a much shorter time than with a fluid coupling.
Figure 8 shows that the maximum torque with the fluid coupling was higher than the maximum torque without the fluid coupling. This seems to be an abnormality as the fluid coupling was implemented to reduce the start-up torque. The reason for this abnormality is attributed to the increased system start-up torque from the inertial load of the fluid coupling itself. The fluid coupling increases the inertia of the system designed from 0.604 kgm22
If a fly wheel was incorporated into the system to match the inertial load of the fluid coupling for the DOL start without the fluid coupling, the results would look similar to figure 9 which illustrates a noticeable increase in the time taken to reach the desired speed, as well as a reduced maximum peak torque. The time taken for the load motor with the fluid coupling to reach maximum speed increases by 30% when compared to the directly coupled motor. These results indicate that a fluid coupling can only be beneficial in a system where the inertia of the coupling itself is small compared to the whole system.
The calculated area under each torque versus time graph is equal to the angular momentum of the system. Assuming that the fluid coupling inertial load is negligible when compared to the system, in other words the total inertia in both cases is the same, the angular momentum for the DOL start with and without the fluid coupling is equal. Angular momentum can be calculated as the product of the angular velocity and system inertia. In this case, the final velocity in both cases is the same, and therefore the angular momentum in both cases is equal. The use of a fluid coupling in a system increases the time taken for the load motor to reach the desired rotational speed, and thus lowers the peak torque to maintain the same angular momentum.
From a power conservation perspective, the peak torque of a high inertial system without a fluid coupling would have a high initial power draw, resulting in a short lived high power usage level. In a system where there are numerous hard-starts, this power draw can accumulate to a significant overall system efficiency loss. The use of fluid couplings allows the motor to run without exceeding its maximum torque rating thereby reducing the overall stress on the system.
The advantages of using fluid couplings to reduce the effect of hard starts are clear from the presented results. An investigation into the continual running efficiency was then conducted.
Figure 10 indicates that the continual running efficiency of a fluid coupling is much lower than that of a standard element coupling. The fluid coupling shows a power transmission efficiency of only 92%, while a solid coupling is closer to 99%. This result indicates that care must be taken when choosing a fluid coupling for few start-ups and long run periods. In this case it may be advantageous to utilise a VSD for soft-start control to avoid the use of an inefficient fluid coupling.
5.2 Motor
Motor testing is a fairly standard practice and most efficiency curves can be obtained from suppliers. To confirm the results obtained, and to directly compare the use of a standard motor versus a high efficiency motor using the same testing apparatus, efficiency curves were generated through testing. It should be stated that the curves obtained in this study resemble a similar trend to the curves obtained from suppliers, however there is a peak efficiency position shift due to a difference in voltage supply to what is indicated in the technical data supplied.
Figure 11 shows the load versus efficiency curve of a standard efficiency Fenner motor and a high efficiency Fenner motor. It can be seen that both motors have a similar efficiency at low loads, however the efficiency drop is noticeably smaller for the high efficiency motor than that of the standard efficiency motor. The motors both seem to be most efficient at 60% of their rated power load. The clear advantage of the high efficiency motor is that the efficiency drop over the increasing load is more gradual, offering a more efficient motor over a larger range of loads.
6 Conclusion
This paper has specifically addressed the efficiency losses of incorporating fluid coupling in systems whose inertial loading conditions are unsuitable. Acknowledging these losses when selecting line items can lead to significant cost savings in electricity expenses and contribute to energy efficiency.
The design of an efficiency testing system, capable of testing coupling misalignment, belt tension, fluid couplings and electric motors was completed, and results were obtained. The development of the test rig was conducted with the purpose of installing it at a supplier's warehouse to generate their own efficiency data for new components. The torque measurement technique and data capturing devices were verified through direct mechanical testing. The motor cradle measurement techniques allow for the measurement of the direct mechanical torque at the drive motor output plus load motor input thus negating any electrical losses within the drive motors themselves. The additional advantage of the designed EcoDyn is the energy recirculation, resulting in energy efficient dynamometer testing - a technique not previously used. In addition to the energy efficiency measurements, the misalignment capabilities of the test rig are unique and able to simulate industrial conditions allowing for multiple degrees of freedom.
Results from the fluid coupling testing indicate the advantages and disadvantages of utilising them in similar systems. Total inertia of the system must be considered before installation. The coupling may not display advantageous properties if the inertia of the coupling itself is significant compared to the overall system inertia. The number of start-ups plus run time are also serious considerations when using a fluid coupling. For long run times, the low efficiency of a fluid coupling may reduce overall system efficiency more than the advantage of reduced start-up torque, and the use of a VSD should be considered in such cases. Of particular interest is the running efficiency loss of 7% when using a fluid coupling in an unsuitable situation.
The testing was able to accurately measure the mechanical efficiency of the electric motors at varying percentage of their maximum load. These tests were conducted for extended periods of time to ensure the motor reached thermal equilibrium, and no further change in efficiency was noted. The test indicated that the high efficiency motor only dropped efficiency by 2% while the standard motor dropped by 4% between a load of 50% and 100%. The unique energy recirculation technique adopted by the EcoDyn system thus resulted in minimal energy consumption for the duration of these tests.
This data can be used to calculate efficiency and cost savings when purchasing correct equipment, and to practise proper installation methods. The correct selection of couplings and motors can lead to reduced electrical costs, and pay for itself over time.
References
1. Eskom, Part 1 Revenue Application: Multi-Year Price Determination 2013/14 to 2017/18, http://www.nersa.org.za, 17 October 2012.
2 Literature Review
- 2. Thopil GA and Pouris A, International Positioning of South African Electricity Prices and Commodity Differentiated Pricing, South African Journal of Science, 2013, 109(7/8), 1-5.
- 3. Department of Minerals and Energy, Digest of South Africa Statistics 2006.
- 4. Veale KL and Roberts LW, Efficiency Management Within an Industrial Environment, Proceedings of the IEEE 18th International Conference on Industrial Engineering and Engineering Management, Changchun, China, 2011, 1859-1863.
- 5. Saidur R, A Review on Electrical Motors Energy Use and Energy Savings, Renewable and Sustainable Energy Reviews, 2010, 14(3), 877-893.
Revised form 22 August 2016
Accepted 22 August 2016