SciELO - Scientific Electronic Library Online

 
vol.24 número3Comparison between two different solution-pumping methods in absorption refrigeration machines índice de autoresíndice de assuntospesquisa de artigos
Home Pagelista alfabética de periódicos  

Serviços Personalizados

Artigo

Indicadores

Links relacionados

  • Em processo de indexaçãoCitado por Google
  • Em processo de indexaçãoSimilares em Google

Compartilhar


Journal of Energy in Southern Africa

versão On-line ISSN 2413-3051
versão impressa ISSN 1021-447X

Resumo

BVUMBE, Tatenda J  e  INAMBAO, Freddie L. Operational evaluation of the performance of a solar powered absorption system in Pretoria. J. energy South. Afr. [online]. 2013, vol.24, n.3, pp.26-32. ISSN 2413-3051.

A 35kW pilot solar powered absorption cooling system was designed and constructed at Moot Hospital in Pretoria to investigate the technical and economic performance of the technology. Technically, the system produced an estimated 43.938MWh of cooling energy per year and reached a maximum power of 31kW and operated with an average COP of 0.63, which compares favourably with the 0.7 given by the manufacturer. This system has since been decommissioned. Unfortunately, due to a lack of standard design and operation information, the system was overdesigned. As a result, the economic performance of this technology could not be accurately determined.

Palavras-chave : solar powered absorption cooling; LiBr-water; system performance; economic performa.

        · texto em Inglês     · Inglês ( pdf )

 

Creative Commons License Todo o conteúdo deste periódico, exceto onde está identificado, está licenciado sob uma Licença Creative Commons